Brand: Apollo
Country of Origin: Taiwan
Model: 2B10K
Type: Online
Capacity: 10kva
Note:
1. The used image is a model image only. The actual product may differ with model image layout, color, size & dimension. No claim will be accepted for image mismatch.
2. The price may be more or less than the mentioned price. Please send a message to the seller for the updated price.
Seller: Orient Computer
Avaiable stock: 10 pc
Sold out: 0 pc
Refund Status: non-Refundable
Warrenty: 12 Months
UPS means Uninterruptible Power Supply and the
explanation behind its name is that it provides a constant power supply without
any conflict. During normal operation and during a power cut, it pulls current
from the AC networks; it supplies current from its backup source. UPS differ
in design types and capacities, so it is hard to decide which one will match
your needs. To aid you with this bad period, we present a thorough summary of
the online Apollo 2B10K Online UPS so that you can reflect on it.
As this online UPS is a type of UPS that
supplies power through the Rectifier and Inverter Pair to the Ac signal in
daily work and uses an inverter to deliver AC power during a failure, the
output power supply still remains on, and no switching is performed. There is
also no lag in the transition in time between its roots. There is no lag for
even a nanosecond in the case of power failure.
True online dual conversion design
Generator Compatible
All Protections over/low-voltage, overcurrent, overload
Intelligent Battery Management, Extended Battery Life
Intelligent Self diagnose function, all kinds of fault protection
Modularized design of subsystems
Bypass back feed protection, battery leakage protection
Parallel Redundancy design, increase the system reliability
Customizable wide input voltage range
Large size input LCD display on the front pane
SNMP for remote monitoring
Model |
2B10K |
Rated Power |
|
Capacity |
10KVA |
Input |
|
Nominal Voltage |
Single Phase, 110Vac~ 290Vac |
Frequency |
50 Hz (60 Hz on
request) ± 5% |
Power Factor |
> 0.98%
(full load) |
Output |
|
Voltage |
220Vac |
Voltage Regulation |
220Vac ± 0.5% |
Transient Response |
± 3~4% under
full load, change and corrected within 2 ms |
Frequency |
50 / 60Hz, ±
0.5% |
Waveform |
Pure Sinewave
THD<3% |
Overload |
Continuous
alarming, switch to bypass, auto recovery upon removing of load |
Power Factor |
0.7 ~ 1
(lagging) |
Overload Capacity |
·
<110% load Continuous ·
110-125% load 12 Minutes ·
125-150% load 10 Minutes ·
>150% load: by pass |
Current Crest Ratio |
3:1 |
Battery |
|
Type |
Maintenance
free lead-acid batteries |
DC Voltage |
192VDC |
Backup time |
15-30 minutes
depending on load |
External Battery |
Up to 8 hours
long time backup depends on external battery |
Supplementary Charger |
Optional
200W/500W charger for extended back-up application |
Recharge time |
5~8 hours |
Cold Start |
Yes, UPS cab be
started without AC source |
Battery Cabinet |
Internal
Battery |
Bypass |
|
Automatic transfer |
on overload and
UPS failure |
Before UPS power on |
Default
"NO", user adjustable to "YES" |
Transfer time |
0ms; less than
4 ms from inverter to bypass and vice versa |
LED/LCD
Indicators |
|
Status |
load
level/Battery level, Battery, Utility power, Inverter, Bypass, Overload,
Fault |
Audible alarm |
Bypass, ON
battery mode, Battery low, Overload, Fault |
Acoustic Noise |
|
At 1 meter
distance |
55 dBA |
Communications |
|
Intelligent
Slot |
Options;
Webpowet, As400 Card or WinPower CMC |
Interface |
RS232 / SNMP |
Software
Management |
AC fault, low
battery, intelligent software for shutdown by remote control |
Environmental |
|
Operating
Temperature |
0 ~ 40°C (32 -
104°F) |
Operating
Humidity |
30 ~ 90%
non-condensing |
Weight |
|
Net (Kg) |
106 |
Dimensions |
|
W×D×H (mm) |
480x340x845 |
Others |
|
Specialty |
·
True on-line dual conversion design ·
Generator Compatible ·
All Protections over/low-voltage,
overcurrent, overload ·
Intelligent Battery Management,
Extended Battery Life ·
Intelligent Self diagnose function,
all kinds of fault protection ·
Modularized design of subsystems ·
Bypass back feed protection, battery
leakage protection ·
Parallel Redundancy design, increase
the system reliability ·
Customizable wide input voltage
range ·
Large size input LCD display on
front pane ·
SNMP for remote monitoring |
Country of
Origin |
USA |
Country of
Manufacturing |
Taiwan |